Voltage drop calculator
Let the calculator do the math so you don't have to do it on a napkin. It's free, there's no sign-up, and it works on your phone.
Awaiting reviewChecked 2026-10-19
Try your own run
Put in your wire, load and distance. You pick the wire, and it shows you whether that choice holds up.
Measuring twice. Calculating once. Drag a slider and watch my bubble.
Voltage drop in short
- Voltage drop is the volts a wire loses on the way to the load. Longer runs and bigger loads lose more.
- A thicker wire loses less. The math uses a constant for the metal: 12.9 for copper and 21.2 for aluminum.2
- You set the target. The tool tells you if the run is at or under it.
- The answer is a check, not a permit. Your local code and the label on the equipment decide what is allowed.
The voltage drop math, step by step
Drop (volts) = 2 x K x amps x one-way feet / circular mils (three phase: use 1.732 in place of 2)12
Worked example
- Take 10 AWG copper, about 10,383 circular mils, feeding a 20 amp load 150 feet away at 240 volts.
- Drop = 2 x 12.9 x 20 x 150 / 10,383 = 7.45 volts.
- Percent = 7.45 / 240 x 100 = 3.11 percent.
- That is over a 3 percent target, with about 232.5 volts left at the far end. Try the next size up.
Wire sizes used here
Circular mils and copper resistance for the sizes in the tool.
| Size | Circular mils |
|---|---|
| 14 AWG | 4,107 |
| 12 AWG | 6,530 |
| 10 AWG | 10,383 |
| 8 AWG | 16,510 |
| 6 AWG | 26,251 |
| 4 AWG | 41,741 |
| 3 AWG | 52,635 |
| 2 AWG | 66,371 |
| 1 AWG | 83,693 |
| 1/0 AWG | 105,535 |
| 2/0 AWG | 133,077 |
| 3/0 AWG | 167,806 |
| 4/0 AWG | 211,600 |
| Size | Ohms per 1,000 ft |
|---|---|
| 14 AWG | 2.525 |
| 12 AWG | 1.588 |
| 10 AWG | 0.999 |
| 8 AWG | 0.628 |
| 6 AWG | 0.395 |
| 4 AWG | 0.248 |
| 3 AWG | 0.197 |
| 2 AWG | 0.156 |
| 1 AWG | 0.124 |
| 1/0 AWG | 0.098 |
| 2/0 AWG | 0.078 |
| 3/0 AWG | 0.062 |
| 4/0 AWG | 0.049 |
Next: the wire chart
ChartWire gauge chart (AWG)Each wire size, with its width and how much it resists current. This checks the math. Your local code and the equipment label decide what is allowed. When in doubt, ask a licensed electrician or your inspector.
Checked 2026-10-19. Next recheck by 2027-10-19.
Sources
- AWG wire sizes: diameter in mils = 5 x 92^((36 - n) / 39), the definition in ASTM B258.
- Copper resistivity of 10.371 ohm-circular-mil per foot at 20 C; the voltage-drop constant K of 12.9 for copper and 21.2 for aluminum is a common design value, shown here as an assumption.